Family owned since 1987

+612 9625 7744

Device Net

Additional information

Description

Sizes

Type/Area of Application
DeviceNet Trunk (Thick)
DeviceNet Drop (Thin)
Cable Construction
1x2x0.96mm² +1x2x1.53mm²
1x2x 0.24mm²+1x2x0.38mm²
DeviceNet™
APPLICATION
DeviceNet™ communication link is based on proven CAN
technology.DeviceNet™ is a bus system developed by Allen
Bradley (Rockwell Automation). These cables are used to
interconnect various industrial devices, such as SPS controls or
limit switches. The special characteristic of this bus system is that
a data pair and a power supply pair are integrated in one cable.
These cables with PVC jacket are designed for fixed installation.
Construction:
Type/Area of Application
DeviceNet Trunk (Thick)
DeviceNet Drop (Thin)
Cable Construction
1x2x0.96mm² +1x2x1.53mm²
1x2x 0.24mm²+1x2x0.38mm²
Inner Conductor Diameter (data pair)
Copper, tinned (AWG 18/19)
Copper, tinned (AWG 24/19)
Inner Conductor Diameter (power pair)
Copper, tinned (AWG 15/19)
Copper, tinned (AWG 22/19)
Conductor Insulation (data pair)
Foam-skin-PE/PE/Cell PE
Foam-skin-PE/PE/Cell PE
Conductor Insulation (power pair)
PVC/ PE/ Cell PE
PVC/ PE/ Cell PE
Conductor Colors 1
light blue, white
light blue, white
Conductor Colors 2
red, black
red, black
Stranding Element
Double conductor
Double conductor
Shielding
Polyester foil, aluminum-lined
Polyester foil, aluminum-lined
Total Shielding
Copper braid, tinned
Copper braid, tinned
Drain Wire
yes
yes
Outer Jacket Material
PVC/ PUR/ PE/ FRNC
PVC/ PUR/ PE/ FRNC
Outer Cable Diameter
12.0 mm ± 0.3 mm
7.0 mm ± 0.3 mm
Outer Jacket Color
Grey/ Violet/ Yellow
Grey/ Violet/ Yellow
Electrical Data:
Characteristic
Impedance@1MHz
120 Ω ± 10Ω
120 Ω ± 10Ω
Conductor Resistance
22.6 Ohm/km max.
90.0 Ohm/km max.
Insulation Resistance
0.20 GOhm x km min.
0.20 GOhm x km min.
Mutual Capacitance@800MHz
39.8 nF/km nom.
39.8 nF/km nom.
Working Voltage
Max: 300V
Max: 300V
Test Voltage
2.0 KV
2.0 KV
Data rate
125 Kbit/s
500m
125 Kbit/s
100m
250 Kbit/s
250m
250 Kbit/s
100m
500 Kbit/s
100m
500 Kbit/s
100m
Attenuation:
125
KHz
<
0.42
dB/100m
125
KHz
<
0.95
dB/100m
500
KHz
<
0.81
dB/100m
500
KHz
<
1.64
dB/100m
1
MHz
<
1.26
dB/100m
1
MHz
<
2.38
dB/100m
Technical Data:
Weight
approximately 195.0 kg/km
approximately 69.0 kg/km
Min. Bending Radius (Laying)
10 x OD mm
10 x OD mm
Operating Temp.Range, min.
- 20 °C
- 20 °C
Operating Temp.Range, max.
+80 °C
+80 °C
ion link is based on proven CAN
llen
are used to
various industrial devices, such as SPS controls or
of this bus system is that
a data pair and a power supply pair are integrated in one cable.
These cables with PVC jacket are designed for fixed installation.
Inner Conductor Diameter (data pair)
Copper, tinned (AWG 18/19)
Copper, tinned (AWG 24/19)
Inner Conductor Diameter (power pair)
Copper, tinned (AWG 15/19)
Copper, tinned (AWG 22/19)
Conductor Insulation (data pair)
Foam-skin-PE/PE/Cell PE
Foam-skin-PE/PE/Cell PE
Conductor Insulation (power pair)
PVC/ PE/ Cell PE
PVC/ PE/ Cell PE
Conductor Colors 1
light blue, white
light blue, white
Conductor Colors 2
red, black
red, black
Stranding Element
Double conductor
Double conductor
Shielding
Polyester foil, aluminum-lined
Polyester foil, aluminum-lined
Total Shielding
Copper braid, tinned
Copper braid, tinned
Drain Wire
yes
yes
Outer Jacket Material
PVC/ PUR/ PE/ FRNC
PVC/ PUR/ PE/ FRNC
Outer Cable Diameter
12.0 mm ± 0.3 mm
7.0 mm ± 0.3 mm
Outer Jacket Color
Grey/ Violet/ Yellow
Grey/ Violet/ Yellow